Door Fan Test Clean Agent Fire Extinguishing Systems
When a suppression system is designed for a room, it’s designed to reach a certain concentration and then hold that concentration for a specific amount of time. It’s ability to hold this concentration is crucial for its ability to put out a fire.
Most rooms, especially server rooms and electrical rooms, have a lot of wiring, conduit, HVAC ducts, and other components coming into the room. All of these penetrations of the walls act as potential areas where the gas can leak out and cause the room to not adequately hold the concentration for as long as it needs to so that it ensures the fire is extinguished.
The door fan test, also called room integrity fan test, is used is to predict the enclosure’s retention time should the buildings clean agent suppression system be discharged.
Upon completion of sealing a protected room, Integrity Room Systems performs a Room Integrity Fan Test to ensure the protected room will hold the agent for the required amount of time. NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, requires that a minimum concentration of 85% of the adjusted minimum design concentration be held at the highest level of combustibles for a minimum period of 10 minutes.
气密性测试;door fan test;房屋密封洁净室门风窗实验;鼓风门气密性测试;气体保护区灭火气体(FM200等)浸渍测试;供应Retrotec防护区气密性测试实验;防护区药剂泄露检测 Retrotec防护区气密性测试实验;空间气密性测试;建筑物气密测试;消防气密性测试;气密性测试气体保护区;房屋气密性测试仪在消防和建筑节能中的应用;消防系统气体保护区封性检测;
Door Fan Test测试服务;IT 机房整体气密性测试服务;建筑物气密性测试服务;气体灭火系统滞留时间测试;气体灭火系统泄漏面积测试服务;换气次数测试服务;洁净室气密性测试服务;被动房气密性测试服务;Leed认证气密性测试服务;港口电气控制柜气密性;换气次数测试服务;消防气密性测试/气密测试;DOOR FAN TEST消防气密性测试;美国Retrotec DOOR FAN TEST;Door Fan Test Clean Agent Fire Extinguishing Systems;气体保护区消防测试/气密测试;房屋气密性测试仪在消防和建筑节能中的应用;化工企业庇护所、安全岛气密性测试服务
公众号
欢迎关注我们的官方公众号
留言反馈